Easy handling and sewing
Fiber count up to 48, higher data transfer capacity
Provides good crush resistance
Large load capacity and long transmission distance
|
Structure |
Position |
Component Type |
Component No. |
Component diameter |
|
Fiber |
G652D |
48 |
||
|
Center |
aluminum tube |
1 |
7.30 mm |
|
|
1st outer layer |
20.3% steel wire |
3 |
2.50 mm |
|
|
40% steel wire |
9 |
2.50 mm |
|
Technical Data |
Complies with IEC, IEEE standards |
||||
|
greased interior |
|||||
|
The braiding direction of the outer layer is counterclockwise (S braiding) |
|||||
|
Cable diameter |
12.3 |
millimeters |
0.484 |
in |
|
|
Cable weight |
383 |
kg/km |
1.359 |
pounds/mile |
|
|
Total support cross-sectional area |
76.12 |
mm² |
0.12 |
in² |
|
|
Cross section area of |
58.90 |
mm² |
0.09 |
in² |
|
|
Al clad steel wire rope |
1 7.22 |
mm² |
0.03 |
in² |
|
|
Cross section area of Alabama pipe |
47.82 |
kN |
10.75 |
pounds |
|
|
Modulus of elasticity (E-modulus) |
107.3 |
kN/mm² |
24,122 |
kpsi |
|
|
Thermal elongation coefficient |
15.7 × 10 -6 |
/ ℃ |
8.72 × 10 -6 |
/ of |
|
|
Maximum work stress allowed (40% RTS) |
251.2 |
N / mm² |
36.433 |
psi |
|
|
Daily stress (EDS) (16%~25% RTS) |
100.5 ~ 157 |
N / mm² |
14.576~22.7 71 |
psi |
|
|
DC resistance (25 °C) |
0.57 |
Ω/km |
0.92 |
Ω/mile |
|
|
Short Current Time (0.5 s) |
10.3 |
ka |
|||
|
Short time current capability (20°C~200°C) |
53.1 |
kA² S |
|||